It has recently come to our attention that Coen Company, Inc.’s first generation iScan flame scanners, if operated improperly at temperatures above the design rating (Overheated Operation), may generate a false flame signal. To ensure that any such Overheated Operation does not lead to unsafe operating conditions, we have elected to replace all existing first generation iScan flame scanners with iScan2 flame scanners, free of charge. The iScan2 flame scanner utilizes an improved detection cell with a higher temperature tolerance and incorporates logic that will shut down the iScan2 flame scanner in the event temperatures in excess of the design rating are experienced. For complete details on how to replace your first generation iScan flame scanner, review the pdf linked here.
|
|
Coen is… Innovation, Tradition, Value.
Since 1912, when we first debuted the revolutionary adjustable tip mechanical oil burner, the Coen name has been a recognized leader in the combustion industry, With a solid foundation of dependable products and engineering capabilities, we’ve spent the last 100 years expanding our expertise in combustion engineering and product solutions around the world. Today, as the Coen Division of John Zink Company, LLC (“Coen”), we will meet the challenges of the next century with the same strengths of innovation, tradition and value that have made Coen a success.
Coen equipment is known worldwide for reliability, efficiency and low emissions and our unparalleled commitment to results-oriented engineering keeps us at the forefront of combustion innovation. When choosing Coen, you can have absolute confidence in your combustion system’s components – achieving better performance, lower emissions and reliable results.